Malibu Hydro...Hydro Basics                                 To index



From water to wire.... how the electricity is generated.          (See below for hydro definitions)
The following text explains the key components in a typical installation.

Water intake:
The process begins with the water in the creek having a potential energy equal to its mass times its height above the turbine mounted on the power house floor. The water is slowed in a pool so the sand can settle out. Larger debris is also filtered out here. Excess water passes over a low weir, or barrier, with a controlled amount entering a large pipeline or 'penstock'.

Penstock:
Water flows down the pipe at a slow rate of speed, typically 5 feet per second. The pressure steadily increases in proportion to the increasing drop. It is the high pressure that forces the water out the nozzle. The actual rate of flow in the penstock is relatively unimportant, unless the pipe is very long in which case an excessive amount of friction is created by the flowing water.

Turbine:
This is the heart of the energy conversion process which changes the waters velocity into mechanical energy. Water striking the curved blades of the turbine imparts its kinetic energy of motion on the blades. The turbine spins at slightly less than one half the jet velocity, and falls away from the turbine with virtually zero energy.

Spear Nozzle:
Manual control of the power produced can be made by adjusting the amount of water passing through the turbine. This is accomplished by adjusting a threaded spear which screws into the nozzle assembly where the penstock enters the turbine. This pinches off the flow in any amount required. Typically, the control is set to the maximum power required, and the governor then maintains control by dumping any excess power.

Generator:
Within the generator there are many coils of wire wound on iron cores attached to the generator frame. Rotating inside these coils is an iron core which produces strong magnetic fields. As the core rotates at 1800 revolutions per minute, the magnetic lines of force pass through the fixed windings. It is this process that produces the alternating current electricity. This same principle is used in all electric generators, from large hydro and nuclear plants to the alternator in your car, although the speed can vary depending on the type of generator used.

Governor:
This is the main controller for the entire system. Precise power line frequency is controlled by exactly balancing the load on the generator with the power delivered to the generator by the turbine. This is accomplished in several ways. Old systems relied on centrifugal force to lift heavy spilling balls against gravity with the amount of lift dependant on the RPM. These weights were linked to an oil based servo drive which activated a spear valve or a jet deflector. This method was subject to a bit of delay, or droop, as it reacted to changing loads.

Modern micro hydro systems sense shaft RPM or power line frequency to govern the speed. This is done by either varying the amount of water hitting the turbine as with the mechanical governors, but providing a faster response time and more precise frequency control. In addition, many stand alone systems use electronic governors which control frequency by rapidly switching on and off ballast loads, usually in a water filled load tank. Ideally, when water is in limited supply, a system will take advantage of both methods.

Load tank:
This is generally made up of a large water tank, or series of separate tanks containing electric heating elements. Excess power is shunted to these elements from the governor thereby "putting the brakes on" the generator. This excess power is often used to heat primary domestic hot water in smaller, separate water tanks, one large central tank, or as a low priority source of heat for a pool or sauna. As lights are turned off in the buildings, the power is immediately directed to the ballast load to maintain the exact balance necessary for precise frequency control. Over the course of the night, large amounts of hot water can be produced and stored for use during the day. This method of frequency control maximizes the hydro plant capacity and reduces or eliminates the need for fossil fuel boilers.

Alarms:
The system alarm panel reports all the conditions of the various components. These can range from bearing temperatures, penstock pressure, line voltages and currents, phase imbalance, generator over speed, unauthorized entry or any other parameter required. Minor alarms are displayed on the panel and relayed to an operator who can respond. In the rare event of a major system alarm, the governor can immediately shut the whole system down by activating a jet deflector which diverts the water jets away from the turbine. The main penstock valve can then be slowly closed by dc motors if required.

Active load Management:
The secret to how a 200 kW hydro plant can provide power to a connected load of 300 kW or more. In addition to the governor controlling the precise speed of the generator and hence line frequency, load management diverts available power to useful loads arranged in a prioritized sequence. The load manager is always testing the power being dumped in the ballast load and when there is sufficient excess, another prioritized load turns on. These consist of water tanks, space heaters, display lighting, dryers, freezers, or any other load that can be shut off for a period of time with no ill effect.
Base loads such as lighting, pumps, outlets, kitchen appliances, sound equipment, computers, communications etc. are always connected. Load management relies on the presence of interruptible loads that can be disconnected at random. In addition, the probability that all available loads will be required is unlikely. The percentage that a generator can be undersized must be calculated by understanding the connected load.


Load Center:
A load center is basically a large switch with up to 24 smaller switches serving as circuit breakers. These will protect the wires and equipment from potential short circuits or overloads. You will have a similar 'electrical panel' in your home. Each building at Malibu has a load center, and each load center will supply power to all the branch circuits in that building.



Definitions used with Micro Hydro
Here is a list of common terms and their explanation.

  • Static head
    The total available drop from intake to turbine nozzle.

  • Net head
    The useable head after subtracting losses from pipe friction etc.

  • Flow
    The quantity of water being used to produce power. This is usually measured in units of cubic feet per second, (cfs) gallons, liters or cubic meters per second.

  • Power
    The rate of doing work, or energy expended per unit of time. Often used inter-changeably, thought not technically correct, with energy.

  • Energy
    The ability to do work, energy can be potential as in water behind a dam being acted upon by gravity. Energy can also be kinetic, that is, the combination of mass times velocity, as in moving water in a penstock or turbine nozzle.

  • Kilowatt
    One thousand watts .

  • Volts and Amps
    The units of electrical pressure and quantity. A typical outlet at home will provide about 15 amps at 117 volts.

  • vars
    The combination of volts and amps acting in a reactive circuit, that is, one that is either inductive, as in the case of a motor load, or capacitive, as in the case of some forms of electronic loads. Vars are like Kilowatts, but since the volts and amps are out of phase, the product of the two is not the same as if they were acting on a non reactive circuit.

  • Ohms
    The unit of electrical resistance. It requires one volt to "push' one ampere of current through a resistance of one ohm. A length of standard 14 gauge house wire would have to be 400 feet long to have a resistance of one ohm.

  • Impedance
    The opposition to current flow as a result of reactive loads. Similar to resistance, but is used in complex AC circuits.

  • Reactive Power
    Energy which is forced back into a circuit as a result of pulses of energy stored in capactive and inductive loads, such as motor coils and some forms of lighting loads.

  • Three phase power
    The most efficient and cost effective way to transmit large quantities of electrical energy. Rather than having two wires carrying single phase power with a 'hot' and a neutral wire as in a typical AC house circuit, three phase systems utilize three wires. Think of it as a one cylinder engine versus a three cylinder engine. Each 'cylinder' (or coil in the generator) has its own wire which runs to the load. Maximum power can be carried at minimum copper cost in this arrangement. Three phase distribution systems are commonly seen along highways on large transmission towers.

  • SCADA
    System Control And Data Aquisition - Radio telemetry used to gather data and control remote systems.